Data centres, cleanrooms and sensitive facilities
C-POLAR and NanoFlashing™ questions, with the company’s answers and the sources they come from.
Last reviewed: .
All questions in this libraryCould the filter introduce particles that matter to a semiconductor cleanroom?
The company publishes no cleanroom classification, no shedding measurement and no packaging cleanliness class.
A requirement of that kind is matched against a named test or found not to be covered by one. The label instructs: “Store flat or on edge in the original packaging, indoors and dry, away from direct sunlight and moisture. Do not stack loads on the media.”
Source: C-POLAR — Validation, https://cpolar.tech/validation/; NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- C-POLAR — Validation
- NanoFlashing™ Air Filter label
Is outgassing characterised for use near sensitive optical equipment?
C-POLAR publishes no outgassing measurement for the material.
The filter is passive. It draws no power, and it has no power supply, electrode, lamp or reservoir. The polarity is a positive electric charge at rest. A requirement of that kind is matched against a named test or found not to be covered by one, and a question about a named material and a named use can be sent to [email protected].
Source: Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, issued by NF Technical Products Inc.; C-POLAR — NanoFlashing™, https://cpolar.tech/nanoflashing/; C-POLAR — Contact, https://cpolar.tech/contact/.
Reviewed on .
Sources
- Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, issued by NF Technical Products Inc.
- C-POLAR — NanoFlashing™
- C-POLAR — Contact
Would the material affect an electrostatic-discharge control programme?
The filter has no electrical connection, and its charge is a property at rest.
The filter is passive. It draws no power, and it has no power supply, electrode, lamp or reservoir. The polarity is a positive electric charge at rest. It is measured as surface charge density, in nanocoulombs per square centimetre.
C-POLAR publishes no assessment of a static-control programme and none of a high-voltage installation. An assessment of that kind is made by the facility that runs the equipment, for the equipment it runs.
Source: Statement of Classification for the NanoFlashing™ Air Filter, NF Technical Products Inc., sections 2.2 and 2.4.
Reviewed on .
Sources
- Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, NF Technical Products Inc.
Can a filter retrofit change a data centre's hot-aisle and cold-aisle balance?
It can: the filter's resistance adds to the pressure the system's fan works against, and the label directs that it is not used where it would restrict airflow beyond the system's specification; what that means for the balance between hot and cold aisles is decided by the design of that system.
The Validation page names Eurovent Certita Certification, Certificate No. 15.06.011, an ISO 16890 ePM1 certification with an A class energy rating. Certificate No. 15.06.011 is on a ten-pocket bag filter, not on a flat panel filter, and a rating belongs to the construction that was tested and to the conditions in the report. The one building energy measurement the company publishes is at a financial landmark in London over six months from March 2024 to September 2024, measured before and after the air handling unit filters were changed to NanoFlashing™. The label instructs: “Do not use where this filter would restrict airflow beyond the system's specification.” It also states: “Improper installation can reduce airflow or damage the equipment.” The label states: “Results in a building depend on the system, the airflow, and how well the filter fits its track.” The filter is specified by nominal size, rated airflow and maximum face velocity.
C-POLAR publishes no pressure-drop curve, no thermal model and no control logic for a building. The design, the redundancy and the alarms of that system belong to the people who run it. Certificate No. 15.06.011 can be looked up at source in the Eurovent Certita Certification certified product directory.
Source: NanoFlashing™ Air Filter label; C-POLAR — Terms of Use, section 6, https://cpolar.tech/terms/; C-POLAR — Validation, https://cpolar.tech/validation/; Eurovent Certita Certification certified product directory, read 19 September 2026, https://www.eurovent-certification.com/.
Reviewed on .
Sources
Does added resistance reduce cooling redundancy during a fan failure?
The filter's resistance adds to the pressure the system's fan works against, and the label directs that it is not used where it would restrict airflow beyond the system's specification; what that means for redundancy when a fan fails is decided by the design of that system.
The Validation page names Eurovent Certita Certification, Certificate No. 15.06.011, an ISO 16890 ePM1 certification with an A class energy rating. Certificate No. 15.06.011 is on a ten-pocket bag filter, not on a flat panel filter, and a rating belongs to the construction that was tested and to the conditions in the report. The one building energy measurement the company publishes is at a financial landmark in London over six months from March 2024 to September 2024, measured before and after the air handling unit filters were changed to NanoFlashing™. The label instructs: “Do not use where this filter would restrict airflow beyond the system's specification.” It also states: “Improper installation can reduce airflow or damage the equipment.” The label states: “Results in a building depend on the system, the airflow, and how well the filter fits its track.” The filter is specified by nominal size, rated airflow and maximum face velocity.
C-POLAR publishes no pressure-drop curve, no thermal model and no control logic for a building. The design, the redundancy and the alarms of that system belong to the people who run it. Certificate No. 15.06.011 can be looked up at source in the Eurovent Certita Certification certified product directory.
Source: NanoFlashing™ Air Filter label; C-POLAR — Terms of Use, section 6, https://cpolar.tech/terms/; C-POLAR — Validation, https://cpolar.tech/validation/; Eurovent Certita Certification certified product directory, read 19 September 2026, https://www.eurovent-certification.com/.
Reviewed on .
Sources
Can the filter be replaced while critical equipment remains online?
The label directs that the system is switched off at the thermostat or at the unit's disconnect before the filter access is opened; how critical equipment is kept running while that system is off is decided by the facility.
The label instructs that the system is switched off at the thermostat or at the unit's disconnect before the filter access is opened, that the filter is fitted into the filter track with the airflow arrow pointing toward the blower, and that it sits square in the track with no gap at the frame. The label states: “Air that passes around a filter is not treated by it.”
C-POLAR publishes no leak-test method and no procedure for changing a filter while equipment runs. What a facility tests, and how it keeps critical equipment online during a change, is decided by that facility.
Source: NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- NanoFlashing™ Air Filter label
Would the product meet a cleanroom's requirements for packaging cleanliness?
The company publishes no cleanroom classification, no shedding measurement and no packaging cleanliness class.
A requirement of that kind is matched against a named test or found not to be covered by one. The label instructs: “Store flat or on edge in the original packaging, indoors and dry, away from direct sunlight and moisture. Do not stack loads on the media.”
Source: C-POLAR — Validation, https://cpolar.tech/validation/; NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- C-POLAR — Validation
- NanoFlashing™ Air Filter label
Can it be integrated into a fan-filter unit without invalidating its tested configuration?
Building the media into a fan-filter unit is the work of the partner that makes that unit, and that partner's own testing decides what the unit can be said to do.
The Terms of Use state: “A prospective partner or manufacturer must perform its own testing, validation, compatibility work, safety review, risk review, and quality controls for its proposed product and use.” The Terms of Use state: “A reported result describes only what the identified test found.” They also state: “A test of C-POLAR material, a component, or a prototype does not establish the performance of a finished product that incorporates it. Construction, processing, storage, wear, cleaning, other components, and actual use may change the result.”
Every commercial NanoFlashing™ product is made by a manufacturing partner, in their facility, in their format. Development runs configuration by configuration, and each partner controls what is said about the work.
Source: C-POLAR — Terms of Use, sections 3 and 5, https://cpolar.tech/terms/; C-POLAR — About, https://cpolar.tech/about/.
Reviewed on .
All questionsDoes the material's fibre shedding change under high continuous airflow?
The company publishes no cleanroom classification, no shedding measurement and no packaging cleanliness class.
A requirement of that kind is matched against a named test or found not to be covered by one. The label instructs: “Store flat or on edge in the original packaging, indoors and dry, away from direct sunlight and moisture. Do not stack loads on the media.”
Source: C-POLAR — Validation, https://cpolar.tech/validation/; NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- C-POLAR — Validation
- NanoFlashing™ Air Filter label
Can the product be used where airborne molecular contamination is the main concern?
C-POLAR publishes no evidence for a gas, a vapour or an odour, and it makes no claim about one; it publishes no cleanroom classification.
A requirement of that kind is matched against a named test or found not to be covered by one. The label instructs: “Store flat or on edge in the original packaging, indoors and dry, away from direct sunlight and moisture. Do not stack loads on the media.”
Source: C-POLAR — Validation, https://cpolar.tech/validation/; NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- C-POLAR — Validation
- NanoFlashing™ Air Filter label
Does the material emit compounds that could deposit on precision lenses?
C-POLAR publishes no outgassing measurement for the material.
The filter is passive. It draws no power, and it has no power supply, electrode, lamp or reservoir. The polarity is a positive electric charge at rest. A requirement of that kind is matched against a named test or found not to be covered by one, and a question about a named material and a named use can be sent to [email protected].
Source: Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, issued by NF Technical Products Inc.; C-POLAR — NanoFlashing™, https://cpolar.tech/nanoflashing/; C-POLAR — Contact, https://cpolar.tech/contact/.
Reviewed on .
Sources
- Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, issued by NF Technical Products Inc.
- C-POLAR — NanoFlashing™
- C-POLAR — Contact
Could a charged surface attract dust during cleanroom installation before operation begins?
The charge is present whether or not air is moving, and the company publishes no measurement of what a filter picks up before a system is started.
The polarity is a positive electric charge at rest. It is measured as surface charge density, in nanocoulombs per square centimetre. NanoFlashing™ attracts negatively charged particles through electrostatic attraction. The filter captures airborne particles mechanically and by electrostatic attraction.
The label directs that the filter is stored flat or on edge in the original packaging, indoors and dry, and that a filter whose media is torn, crushed, wet or visibly damaged is not installed.
Source: Statement of Classification for the NanoFlashing™ Air Filter, NF Technical Products Inc., sections 2.2 and 2.5; C-POLAR — NanoFlashing™, https://cpolar.tech/nanoflashing/; NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.5, NF Technical Products Inc.
- C-POLAR — NanoFlashing™
- NanoFlashing™ Air Filter label
Can an installed filter be checked for leaks using the facility's established inspection system?
The label sets the steps for changing the filter, and the inspection of an installed bank is the facility's own.
The label instructs that the system is switched off at the thermostat or at the unit's disconnect before the filter access is opened, that the filter is fitted into the filter track with the airflow arrow pointing toward the blower, and that it sits square in the track with no gap at the frame. The label states: “Air that passes around a filter is not treated by it.”
C-POLAR publishes no leak-test method and no procedure for changing a filter while equipment runs. What a facility tests, and how it keeps critical equipment online during a change, is decided by that facility.
Source: NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- NanoFlashing™ Air Filter label
Does a laboratory's containment airflow depend on a filter classification this product lacks?
The company publishes no cleanroom or containment classification for the filter; the ratings published on cpolar.tech are MERV 15A (LMS Technologies, Report 6847, a 24 × 24 × 30 in. pocket filter) and ISO ePM1 70% (Eurovent Certita Certification, Certificate No. 15.06.011, a ten-pocket bag filter), and the filter class a laboratory's containment airflow needs is set by that laboratory's own design.
A requirement of that kind is matched against a named test or found not to be covered by one.
Source: C-POLAR — Validation, https://cpolar.tech/validation/.
Reviewed on .
Sources
Can a data centre's control system distinguish a failed fan from a restricted filter?
How a system behaves when its filters change is decided by that system, and the label sets the filter's own limits.
The Validation page names Eurovent Certita Certification, Certificate No. 15.06.011, an ISO 16890 ePM1 certification with an A class energy rating. Certificate No. 15.06.011 is on a ten-pocket bag filter, not on a flat panel filter, and a rating belongs to the construction that was tested and to the conditions in the report. The one building energy measurement the company publishes is at a financial landmark in London over six months from March 2024 to September 2024, measured before and after the air handling unit filters were changed to NanoFlashing™. The label instructs: “Do not use where this filter would restrict airflow beyond the system's specification.” It also states: “Improper installation can reduce airflow or damage the equipment.” The label states: “Results in a building depend on the system, the airflow, and how well the filter fits its track.” The filter is specified by nominal size, rated airflow and maximum face velocity.
C-POLAR publishes no pressure-drop curve, no thermal model and no control logic for a building. The design, the redundancy and the alarms of that system belong to the people who run it. Certificate No. 15.06.011 can be looked up at source in the Eurovent Certita Certification certified product directory.
Source: NanoFlashing™ Air Filter label; C-POLAR — Terms of Use, section 6, https://cpolar.tech/terms/; C-POLAR — Validation, https://cpolar.tech/validation/; Eurovent Certita Certification certified product directory, read 19 September 2026, https://www.eurovent-certification.com/.
Reviewed on .
Sources
Can data-centre filters be included in rack-level thermal models without treating the whole room as uniformly mixed?
How a system behaves when its filters change is decided by that system, and the label sets the filter's own limits.
The label instructs: “Do not use where this filter would restrict airflow beyond the system's specification.” It also states: “Improper installation can reduce airflow or damage the equipment.” The label states: “Results in a building depend on the system, the airflow, and how well the filter fits its track.” The filter is specified by nominal size, rated airflow and maximum face velocity.
C-POLAR publishes no pressure-drop curve, no thermal model and no control logic for a building. The design, the redundancy and the alarms of that system belong to the people who run it.
Source: NanoFlashing™ Air Filter label; C-POLAR — Terms of Use, section 6, https://cpolar.tech/terms/.
Reviewed on .
Sources
- NanoFlashing™ Air Filter label
- C-POLAR — Terms of Use, section 6
Can a museum archive assess off-gassing risks to paper and photographic collections?
C-POLAR publishes no outgassing measurement for the material.
The filter is passive. It draws no power, and it has no power supply, electrode, lamp or reservoir. The polarity is a positive electric charge at rest. A requirement of that kind is matched against a named test or found not to be covered by one, and a question about a named material and a named use can be sent to [email protected].
Source: Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, issued by NF Technical Products Inc.; C-POLAR — NanoFlashing™, https://cpolar.tech/nanoflashing/; C-POLAR — Contact, https://cpolar.tech/contact/.
Reviewed on .
Sources
- Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, issued by NF Technical Products Inc.
- C-POLAR — NanoFlashing™
- C-POLAR — Contact
Does installation near high-voltage equipment require a separate electrical compatibility review?
The filter has no electrical connection, and its charge is a property at rest.
The filter is passive. It draws no power, and it has no power supply, electrode, lamp or reservoir. The polarity is a positive electric charge at rest. It is measured as surface charge density, in nanocoulombs per square centimetre.
C-POLAR publishes no assessment of a static-control programme and none of a high-voltage installation. An assessment of that kind is made by the facility that runs the equipment, for the equipment it runs.
Source: Statement of Classification for the NanoFlashing™ Air Filter, NF Technical Products Inc., sections 2.2 and 2.4.
Reviewed on .
Sources
- Statement of Classification for the NanoFlashing™ Air Filter, sections 2.2 and 2.4, NF Technical Products Inc.
Can spare filters retain cleanroom cleanliness through ordinary warehouse handling?
The company publishes no cleanroom classification, no shedding measurement and no packaging cleanliness class.
A requirement of that kind is matched against a named test or found not to be covered by one. The label instructs: “Store flat or on edge in the original packaging, indoors and dry, away from direct sunlight and moisture. Do not stack loads on the media.” NanoFlashing™ is a technology; the name, rating and sale of a product that carries it are set by that product's maker and seller.
Source: C-POLAR — Validation, https://cpolar.tech/validation/; NanoFlashing™ Air Filter label.
Reviewed on .
Sources
- C-POLAR — Validation
- NanoFlashing™ Air Filter label
Would replacing only part of a filter bank undermine uniform room airflow?
It can: each filter's resistance adds to the pressure the system's fan works against, and the label directs that it is not used where it would restrict airflow beyond the system's specification; what that means for a partly replaced bank is decided by the design of that system.
The Validation page names Eurovent Certita Certification, Certificate No. 15.06.011, an ISO 16890 ePM1 certification with an A class energy rating. Certificate No. 15.06.011 is on a ten-pocket bag filter, not on a flat panel filter, and a rating belongs to the construction that was tested and to the conditions in the report. The one building energy measurement the company publishes is at a financial landmark in London over six months from March 2024 to September 2024, measured before and after the air handling unit filters were changed to NanoFlashing™. The label instructs: “Do not use where this filter would restrict airflow beyond the system's specification.” It also states: “Improper installation can reduce airflow or damage the equipment.” The label states: “Results in a building depend on the system, the airflow, and how well the filter fits its track.” The filter is specified by nominal size, rated airflow and maximum face velocity.
C-POLAR publishes no pressure-drop curve, no thermal model and no control logic for a building. The design, the redundancy and the alarms of that system belong to the people who run it. Certificate No. 15.06.011 can be looked up at source in the Eurovent Certita Certification certified product directory.
Source: NanoFlashing™ Air Filter label; C-POLAR — Terms of Use, section 6, https://cpolar.tech/terms/; C-POLAR — Validation, https://cpolar.tech/validation/; Eurovent Certita Certification certified product directory, read 19 September 2026, https://www.eurovent-certification.com/.